30amp Socket, 15amp Compressor

I have a 30amp wall socket in my garage, connected to two 20amp fuses in my garage sub box. I bought a 60 gallon air compressor rated 230v 15amp (non-reversible???). I am under the impression that I can use this compressor with the socket I have. The compressor did not come with a plug but did have the wires. One red, one green, one white. The plug I bought to the match the socket has instructions for one black wire (hot) one green (ground) and one white (neutral) I guess my question is, would the red wire be my hot wire? Does everything else sound ok?
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

I bought a LED fixture that fits in a 4inch can

http://indoors.pricegrabber.com/show...s/m/928501559/



The thing iswhen I pushed the fixture in I niked the black wire from the can's socket. What should I do replace the socket or should I just take the can's socket out and also the LED socket out and use marettes?   The thing is I don't have much cable from the box the romex is about 6 inches long and was cut to lenght!!!
      
Hello everyone,I have a question about a forklift battery charger i bought. Ok,its an exide forklift battery charger 36 volts. It weighs a ton so i am having to run a 25 foot extension cord to it. My question is,my 220 wall outlet has three holes so i went to lowes and made a 220 extension cord. Now i get to the ac cable coming out of the charger that hooks to the extension cord(plug was cut off),there are 4 wires coming out of the cable green,white,red, and black......the guy at lowes said i could buy a 3 prong plug for it to plug into the female end of the extension cord because one of the 4 wires is probably neutral and i wouldnt have to hook up but the green,white and either the red or black.....is he right? Inside the charger the red,white and black all go to big fuses and green to ground. Also above the fuses it says "factory set to 480 volts ac". I guess my question is,will this charger only work using a 4 prong wall outlet(mine only has 3) and with 4 prong plug hooked to cable coming out of the charger itself or is the guy at lowes right in saying that only the red OR black wire has to be used? Sorry if this is confusing but ive searched and searched online for 3 days and havent found anything. Thanks in advance for any help-Kevin
      
I have a 5 hp, guess it's a 80 gallon, 220 volt Ingersoll Rand compressor and had problems with the motor not wanting to start. I found a replacement box that included the Siemens starter and a new reset. The only thing this new box doesn't have is the two 5 amp fuses and didn't figure I needed to use them so I didn't add them to the new box.(?) After wiring the unit I have found the only way the compressor will kick on is if I hold down the Siemens starter re-set.



I know I have the motor wired properly and the wires from the pressure switch expect the white one. It originally went to one of the two fuses and than to where I currently is.(?)



The black motor wire was connected to the bottom of the reset (lower left), which is out of view in the pic

The white motor wire was connected to the bottom right of the Siemens starter

The motor ground was connected to the ground terminal on the box.



The pressure switch black wire was connected to the top right of the starter.

The pressure switch with wire was connected to the top left of the starter.

The ground was connected to the ground terminal on the box.



The incoming black hot wire was connected to the top left of of the starter.

The incoming white hot wire was connected to the top right of the starter.

The ground was connected to the ground terminal on the box.



Any idea what's wrong and have I included enough information?



Thanks, Shawn
      
I'm getting ready to dig a trench to run electricity from my house to my garage.  Along with an electrical line, I would also like to run a line for my air compressor.  I would like to keep my compressor in my basement and have a line for it in the garage.  Does anyone have any tips for how to properly bury an air compressor hose?  I searched on Google a bit, but couldn't really find exactly what I was looking for.  Thanks.



Jesse
      
My house has 240v outlet from the previous owner for a kiln of some sort. Im putting a tanning bed in its place. The plug on the tanning bed is a L6-30. I checked specs on the tanning bed and it requires a L6-30 recepticle and a 30amp circuit breaker. I went to the local home fixit store and found the correct recepticle and bought a 2-pole Siemens 30a circuit breaker. After shutting off the main breaker and using testing equipment I pulled out the 50a breaker and replaced it with the 30a..no problem. Heres where Im not sure....The L6-30 recepticle that goes in the wall has a X and a Y and a G marking on it. The G is grounding per instructions, w is white or grey, and X,Y,Z are black, red, blue or etc etc.The wires that come out of the house are red, black and a bare aluminum bradied type wire. Looking at the back from the top counterclockwise  I hooked up the red, then black, then the bare nraided to the G (has green screw) Is the black and red correct? And why doesnt it say red, black and gound?  Can anyone shed some light on this? Thanks!!!
      
I am in the process of installing a submerisble pump into my well, but I have a few questions I'd like answered first.



The pump is a 1HP, 230V pump with 8.2amps and KW 0.75.  It is rated at 12/2 w/ ground. 



1) Is there any reason I shouldn't install a 230v wall mounted switch to turn this on/off if I want to kill the power.  For now a pump start will control it for my irrigation system, this would just be in addition if I ever wanted to shut things down and not have to rely on using the breaker, which I understand shouldn't be used as a switch.



2) What about installing this on a plug, so that I can plug it into a receptacle vs. hardwired.  (*I'll explain my reason later)



3) My understanding is 12gauge wire is rated for 20amp, but it looks like the owners manual calls for a 25amp fuse.  Should I use 20amp or 25amp?



*The reason I ask about the switch and the plug is because I plan on using some wiring that is already in place.  I already have 12/2 w/ground installed in the location of the pump start.  It is currently wired for 110v as it was placed there for a 3/4hp jet pump I planned on installing, but ended up going with a cased well instead, so I figure why not utilize the existing wire, but switch it to 220 instead of 110.  Basically, swap the 20amp 110v switch out for a similar rated 230v switch and replace the receptacle with a 230v receptacle and just plug this pump in. 



I question the use of the plug because I thought I had read somewhere it was ok to use one, but when unpacking the pump last night, I thought I read never to install it on a plug, so now I'm unsure.  Why would they not want it on a plug?  I guess it's not a big deal as I can always run wire into the j-box, but I hate using pigtails if I don't have to.



Thanks for any info on this...heading to the parts store in a while to grab the fuse and anything else I need.
      
I built a shed and wired it.

I used #8 direct burial from the house to the shed.

I have a breaker in the house 15 amp for just my compressor.

When i run the compressor i seems to drain power from everything else,

ex: all light in the hose fad, my filter on the fish tank stops.

Could some one help me figure this out and put a stop to it.



Thanks Dak
      
I have a fan assisted oven which draws about 12A maximum but the nearest socket outlet is already part of a ring main which is pretty fully loaded so I decided that it'd be best to plug it into the other ring main in my house and the nearest socket is about 15metres away, would a 2.5mm flex be ok for this or should I opt for a 4mm? Or would a 4mm have a knock on effect on something else
      
I had a previous thread about bonding my inground pool. I had it done yesterday. I set up all the plumbing for my filter and I am going to wire it up tomorrow.

This pump was wired up once before and it is being moved. All the wiring was removed when the contractors were breaking up the concrete. It has a 25 amp breaker that I am going to replace with a GFI 25 amp breaker. I am going to wire it from the breaker box to a switch (1 foot from the box) to the receptacle about 45 feet away. I am going to use 12 gauge solid wire. I am not sure which would be better. Should I use 12/3 romex and use one as the ground or use 3 separate wires colored white, black and green. Also they had the green wire going to the ground bar in the breaker box. I guess I will attach the green(ground) wire to the ground bar and then run it to the green lugs on each receptacle.  Also which types of boxes would be best to use metal or plastic. I am going to be using plastic pipe to run the wires.
      
I am trying to install a SunSmart Digital Timer to my hall lightswitch (single pole). The timer has 5 wires: Black, White, Blue, Red, and Green. My switch box only has 3 wires: Black, White, and the bare ground wire. I connected the black to the black, white to white, and green to the bare ground. I have power to the timer but the light doesn't work. What should I do with the blue and red wires? Right now I have each capped off. Thanks.