Need Help With Wiring

I have a light switch in my kitchen that is not being used.  I plan to use it for a new light that will be installed over the counter.  The switch box has a 3 way wire that is live. I have a basic current tester that lights up "110 V" when it detects a live circuit.  When I use my circuit tester to test for current in the black wire (with neutral), it barely lights the tester.  When I test the red wire (with neutral), there is no current.  When i test the red and black together, the tester lights up nice and bright.  So I am a little confused.  I do not need it to be 3-way, this switch will only control one light.  Any advice on how to wire this?



Thanks!
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

I have an outdoor light fixture that I am trying to replace.  The house was built ten years ago.



When I removed the original lamp, I noticed one of the two leads was wired to the ground, and one was wired to the black wire, which is hot per my current sensor.  There are three wires in the box - black, ground (bare copper), and white or neutral, all from a single romex cable.  Unfortunately, I do not recall where the white was when I removed the original. 



I wired the new lamp per the instructions, something I have done many times before - black to black, white to white, and bare copper ground to ground.  Nothing.  The lamp and bulbs are brand new, and I have tried four separate bulbs.  I checked the black and neutral with my current sensor and with the switch on and the lamp installed this way, both show as hot. With the lamp not installed, the switch on, and the wires disconnected only the black shows as hot.  The switch is single pole, and appears to be wired correctly with a black to each screw on one side and a copper ground on the other.



Assuming the new fixture was bad, I reinstalled the old fixture correctly -  black to black, white to white, and bare copper ground to ground.  Still nothing. No light, and I confirmed the bulb is good by putting it in another lamp.   The only way to get it to light is to connect the neutral in the lamp to the bare copper ground.



I capped the wires, turned the circuit back on, and identified all the outlets, switches and fixtures on the same circuit.  I opened every one of them up (four lights and eight outlets) and found three (one switch and two fixtures in another room) where multiple commons connect.  All were properly connected.  My outlet tester shows all outlets as "correct".  I found no instances of grounds connected to commons or vice-versa.



Any ideas?  Is it proper to wire this thing the way I found it?



Thanks for any and all advice!
      
We had a pipe disconnect above the downstairs bathroom and the ceiling just about came down, so I decided since it was a hedious looking space, that it was a sign from the gods: Reno time!



Im now at the wiring stage. Originally there was a junction box with a light fixture out one side and a single pole switch(no ground screw...grnd wire attached to the box)on  the other. Typical set up: white from switch marked "hot" or "black" at both ends, and spliced with the incoming power's black wire. Then remaining blacks are spliced together as are the remaining whites... grounded accordingly.



What Im trying to do now is add a GFCI receptical to the mix. But Im having some trouble figuring it all out. NOTE: light fixture is not installed yet, just the wire for it with the ends capped off with a wire nut on each of the wires (Wht/Black/Grnd)



First, whats in the walls: Circuits on a 15 AMP fuse with older (but not the oldest) 12/2 wire with a blue weaved fiber outside cover. Still looks to be in great shape. I've continued using newer, yellow (Lomex or Romex?) 12/2 from homedepot as I've read that you should not mix 14 and 12 together.

All that is on the cicuit is 3 pot lights with 65w bulbs, single bulb on the stairway and what ever goes in the bathroom, so from my math, there should be plenty of room left on the circuit.



What I've tried so far:

A: I spliced the "hot"/"black" white wire from the switch to the incoming power's black, like before. Then I spliced all remaining blacks together with a wire nut, then the same with all remaining whites and then all grounds (did not attach any grnd wire to the Junction box).



Result, Nothing. After switching on the power, I tested the GFCI with a voltage tester as well as the switch and got no read.



B: Undid everything, re-spliced all like to like: all blck together, all white together..etc.



Result: Fuse trips.



Im no electrician, which I imagine is blatantly obvious from the above post, but I am following a Homedepot wiring manual, its just that what Im trying to do is not really addressed in the book... at least not directly. So I've been trying to figure it out by reading every single page, but Im still at a loss.



I've attached a very basic diagram of what is there right now. Any advice would be most appreciated.

Thanks in advance,

John
      
Hello,



I currently have one light switch which operates an outlet in one of my bedrooms.  I want to add a ceiling fan that has independent switches for the fan and light - but I want to make sure i'm wiring it correctly and safely.



Current (First Pic)- Live hot feeds into bottom of switch (bottom insert hole) and the all of the bedroom outlets (pig-tailed) tie into the bottom of the switch on the screw.  Coming out of the top of the switch is one hot which feeds to a single outlet.  All of the neutral and grounds are tied together.



New Plan (Second Pic)- Remove the constant outlet hot from the screw, add a new hot wire to the top of new switch and run a wire up to the attic for fan.  Add another hot wire from the bottom of that switch to the third switch and run another wire up to the attic for the lights.  Re-connect the constant outlet wire to the screw of the last switch.  Connect all the neutrals and all of the grounds together.



At the top of the ceiling, connect the neutrals and grounds together with the fans neutral and ground.  Connect the fan hot to the fan switch hot, and the fan light hot to the light switch hot.
      
Going through a crazy heat wave here in SoCal, and one of my tenants called to tell me that the electricity isn't on in some of his rooms. He turned on his portable AC unit that he has been using all summer and something may have happened.



Downstairs:The dining room light switch, downstairs light switch do not work. All outlets around them do work though, which is odd cause I would have thought they'd be on the same circuit.



Upstairs: The side bathroom light switch does not work, but outlets all work. In the master bedroom (where the AC unit is located), the master bathroom light switch does not work, nor does the master bedroom light switch. All of the outlets do not work either. I used my outlet tester and it gave me the hot/ground reversed lights. I think this means that the white/black wires are reversed on the outlets (has not changed recently).



I went over, checked all of the breakers. Switched them to off, then back on, did not fix the issue. All breakers stay in the on position without tripping, so no shorts?



Checked all GFCI's, hit test, then reset, did not solve the problem.



We unplugged everything from all outlets, and retried, but it didn't work.



I checked continuity between the main power lines, and the output of the circuit breakers, and all were fine. I did NOT check the voltages though, and will do so in the morning when I stop by again.



Is there anything else I should check?
      
Hi all, this is my first post, so...my kitchen was just renovated and the electrical outlets are on the walls and I wanted them in plugmold under the cabinet. Why didn't it happen?  Long story, but I'm doing it myself now.  The electrical receptacles are on 2 separate circuits with a gfci receptacle on each and neither circuit has a receptacle outside the kitchen where I can put the gfci's, so I'm putting gfci breakers in the panel instead. I've run into a different problem on each circuit that'd like some advice on.



Circuit 1: this is a 20 amp circuit.  I have to plug this circuit's neutral wire into the gfci breaker, but I couldn't see which neutral wire matched the hot wire (buried in mess of wires) and I don't have a continuity tester so I just pulled one neutral at a time (tedious) until the circuit failed, but it never failed. So I did this again for every neutral...same result. This circuit shares a few boxes with other circuits so I'm wondering if the neutrals on different circuits are tied together somewhere, and if so I'm pretty sure, but not completely, that that's not going to work with the gfci breaker.  So I didn't install that gfci breaker since I'm not confident it would actually gfci (yep i verbified gfci).  What do you think?



Circuit 2:  this is a 20 amp circuit.  This circuit currently has the refrigerator, gas stove and range hood, and then a gfci in front of 3 electrical receptacles, which already sounds bad since I thought the kitchen receptacles required 2 dedicated circuits. I replaced that breaker with no problem, but it tripped after a few minutes and continued to trip every few minutes. I haven't changed anything else on that circuit yet and it's never tripped before, but now it is, so I put the old breaker back for now. The current gfci receptacle is only protecting the 3 outlets since the appliances are ahead of it. I know you wouldn't normally want the appliances gfci protected, so do you think the refrigerator motor may be a problem?  Do I need the appliances on a separate circuit?  What would you suggest I do?



Thanks, and if you're wondering "why all the effort?", it's partly because I'm meddlesome, partly because I'm bored, and partly because the backsplash tile is to be on showcase, not the electrical receptacles.
      
I'm trying to fix a problem with a track light installment over the a bar I've just put in. I've done it before. never had issues. but this particular problem is driving me nuts. It just defies logic.  The electrician who actually installed the associated dimmer switches with this dining room area was called as it seems it may be a flaw with his wiring, but he's blown us off and I have to try and solve this myself.



This is how it's all set up. I've been rehabbing our home from top to bottom, and converted our old kitchen into a dining area. Within this dining area are four sets of lights, all controlled from one box containing four dimmer switches. I set up all the new wiring and installation of the lights in the ceiling, and we paid an electrician to come in, check everything out, set up the multiple switches, and connect it all to the board. It's all new copper wiring from beginning to end, as I didn't want to connect or splice in to the old aluminum wiring that was in place. All the new wiring and lights are on a dedicated 15 amp breaker. Three of the sets of lights were set up to be available from the day the electrician came around. The fourth, for the track light over the bar, was left hanging from the ceiling capped off and with the switch off, as I still had work to do installing an overhead wine rack, under which the track was going to be set.



Two days ago I finally got around to putting the track up, but after setting it in place and connecting the power up the lights wouldn't work. I took the lights out to our kitchen, where I installed another track light system some time ago, plugged one of the lights in, and it worked just fine. I then went back to the bar area and used a spare track, then a spare connector, to see if I could isolate the fault, yet neither of the items provided a solution. Now here's the weird bit - every time I tried checking the system out, I'd get 120 volts showing from the wiring and from the track when I'd test with the multimeter. But the second I'd put a light into the track, the multimeter would drop to zero on the voltage reading on either the wiring or the track. Take the light fixture back out, and the voltage would pop back up. Inserting the light was thus completing some kind of odd loop. It wasn't just one light - I double checked by grabbing working lights from the kitchen track and inserting them into the other track - the same problem would pop up. Finally, having come to the conclusion that there was nothing wrong with the track at all, I took the whole assembly over to a nearby wall outlet, used some spare electric cable to connect up to the appropriate slots - presto, the light came on! I even double checked all this by grabbing another light fixture destined for our bathroom, and tried connecting it to the wiring over the bar. Nothing. Yet as with the track light, the minute I took it over to the wall outlet and connected it, the light worked.



So everything logically points to the fact it has to be something to do with this individual circuit, right, because a) the light fixtures work when plugged into another circuit and b) the other three dimmers and lights hooked up in the same box work fine and draw power from the same wire cable/breaker combination. The only things left that I can think of is that the electrician has either wired the dimmer switch up incorrectly or that there's some kind of flaw inside the switch itself. Does this make sense?



A friend also told me to double-check to make sure that the black wire feeding power to the light was indeed the hot wire, and it is.  If I touch it with the black test lead from the multimeter and put the red one to the neutral I show 120 volts. If I keep the black test lead on the black wire and put the red test lead to the ground - I also show 120 volts.



A final point. I know I'm not overloading the circuit - not even close. With all four dimmers maxed and every light on - including the test light on the track - I'd only be drawing 8 amps on a 15 amp breaker, besides which I'm only using one set of lights while I'm working on this problem anyway. This is a dedicated circuit, so there's no additional power being drawn away by something else.



So how am I getting 120 volts from this wiring, according to my multimeter, yet it won't light up ANYTHING and keeps giving off the indication that some kind of loop or short is being created every time I actually plug a light into the track? It's got me totally stumped.



Anyone have any ideas?
      
this topic came up on another thread but its buried pretty deep. it is my understanding from several experienced posters that under normal circumstances all neutral current should flow back to the utility neutral, not the grounded plumbing or rods.



i am trying to figure out why. bear with this simplistic example.



100a service - 3 wires in - A (hot+), B (hot-) and N (neutral).

circuit 1 on A is using 12 amps

circuit 2 on B is using 7 amps

so a total of 5 neutral current amps have to go somewhere.



they could all flow back on N, but if bonded to N at the panel is a low resistence connection to say, copper water pipes, wouldnt some of the current flow there?



is the utility neutral supposed to be so low resistence that none of the current would flow to the grounds? if that is the case i need to call my utility ASAP because a considerable amount of current flows to my main ground.



where i am struggling is i dont see how a utility pole or transformer would be any lower resistance than miles of metal plumbing and since they are bonded together, the current can choose (i know wrong word but im not an electrican or an engineer) either path
      
I am trying to replace a rocker switch that runs my Panasonic bathroom exhaust fan with a programmable switch that allows me to run the thing automatically several times a day to help suck moisture out of the condo (it's a 1962 condo with concrete walls, aluminum windows, and no central air).



I initially bought a GE SunSmart Timer but it requires a neutral, which I don't think I have. I understand there are some other switches like Intermatic ones that don't require neutrals.



I don't think I have a neutral because the condo is old and I don't see a white wire in the box, but what's strange is that I do see an unconnected orange wire in there. Does anybody know what that could be? Image is attached. Essentially there are 2 blues, 1 red, 1 black, and 1 orange (unconnected) in there. The only thing I can find about orange wires is something called a "high leg delta" circuit, which seems reasonable because it's supposedly used to control fans and lights off the same circuit, which is exactly what's going on here (one can light, one heat lamp, and one fan).



Any ideas?
      
Older house with the metal enclosed wiring has stumped me.  I am attempting to add a second switch for a fan off existing light switch in bathroom.  Existing wiring:  W,B,R from panel, W,B to light.  2 white wire are tied together, two black wires to one contact and red to other contact on switch.  Disconnected all wires and confirmed the black is live from panel.  It seems to me the light is seeing power the entire time since the blacks are connected? I'm confused, please help. how do I add another switch onto this circuit?  Thanks!
      
I completed my whole house rewire last Fall (took 2 years and severely tested my wife's patience). I read 5 wiring books in the early stages but read Rex Cauldwell's Wiring a House with his above code suggestions near the end of the project and now im obsessing about some of the stuff I didnt do. What do you guys think of some of the suggestions, specifically,



1. Driving 8 ground rods and the wire must be continuous (I drove 4 but the #6 copper wire from the panel to rod 1 is 1 wire and the #6 wire from rod 1 through rod 4 is another wire but both are properly clampled to rod 1 with an acord clamp). Funny, even with 4 rods there is almost no current through the rods versus 2-3 amps through the traditional cold water pipe ground



2. 1 circuit for each duplex receptacle in bathrooms. Since I have a quad in each of the batchrooms, that would be 4 circuits instead of 1 (code allows an unlimited number of bathroom receptacles on one circuit which does seem odd)



3. Nothing shared with kitchen counter receptacles (ie kitchen wall and dining room on their own)



4. Dedicated circuits for everything - I added dedicted circuit for fridge, microwave and dishwasher/disposer, but did not separate the dishwasher disposer onto 2 circuits. There used to be what I called "Circuit X" which did kitchen counter, microwave, dishwasher, disposer, fridge, 2 kitchen counter outlets, dining room and 1 outside outlet. Wife frequently blew that one. Circuit X was divided into at least 5 circuits during the rewire



5. No switch loops - did 5 of these to save on carpentry/avoid certain box fill problems. Now 2011 code says no switch loops without a neutral. Oops?



Just wondering what you guys think.