Strange Wiring Problem In My Dining Room.

Hey guys and gals,



got a very odd dilemma, in my dining room there is a chandelier lamp that is controlled through a dimmer switch(even though it is not a dimmer). There is also a closet with a light switch as well.



The odd circumstance i am having is when the closet light is on(via its own switch), and you turn on the dinning room light, the closet light goes out. Then if you turn the dining room light off,the closet light turns back on.



The closest light switch has zero effect on the dining room light, the dining room light seems to have control over the closet light and dining room light.



Any ideas on a fix. I was thing just replacing the dimmer(once again does not actually dim) with a single pole interrupter. I just dont want to burn my house down
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

I am currently remodeling a bedroom in my home for a new baby.  I have gutted the room and am replacing all the electrical and adding new recessed lighting.  The room will also have a ceiling fan, along with the recessed lighting.  I am looking for a single gang light switch that will operate the ceiling fan independently of the recessed lighting, with a dimmer for the recessed lighting.  I don't have room for a double gang box where the switch is currently placed, as there is a closet in the way.  Is there such a thing as a switch that will operate the ceiling fan and it's lighting on a normal on/off switch, with a dimmer that can independently control the recessed lighting?  I have checked with the local big box stores and everyone has told me I will have to run two switches.  Is this the case?  Any info would be greatly appreciated.  Thanks in advance.
      
We are just beginning to start with our kitchen remodel. Today, I mapped out all the circuits and this is what I found.



Circuit # 7 - 20 amp circuit to 1 back splash outlet then to 3 kitchen wall outlets, then to a closet outlet and closet ceiling light and then to a side  porch light!



Circuit # 8 - 20 amp to Dishwasher and Disposal



Circuit # 9 - 20 amp circuit to microwave and kitchen ceiling lights. 2 patio recessed lights and dining room ceiling light.



Circuit # 12 - 20 amp circuit to another back splash outlet then to 2 dining room wall outlets.



Circuit # 14 - 20 amp to Refrigerator only



Circuit # 18 - 15 amp to GFCI outlet in garage then that feeds 3 outlets for 3 bathroom outlets and 1 outside patio outlet.



I going to have to add 1 more back splash outlet due to increase in counter space. I'll put the microwave on a dedicated circuit. So I need 2 additional breakers but I only have 1 blank spot in the breaker panel. I guess I can add one of those slim tandem breakers.



So my question, is it ok to have additional wall outlets on the same circuit as a back splash outlet?  If it's ok I'll lighten up circuit # 7 by putting some of those wall outlets on the additional back splash outlet.

Oh, I have 2 20 amp circuits I did not get identified yet! I'll get to those tomorrow.



thanks!
      
I am working on fixing an issue with the wiring in one of the bedrooms in my older mountain home. Though I was not present for the cause of the problem, here is what was told to me by the tennant.  he claimed that he went to turn on the light in the closet, (a 3 lamp track bar light, wired to a switch) he heard a loud pop from the light in the closet and lost power to to the room. The room has 6 recessed ceiling lights on 2 separate switches, presently only half of the lights work.There are no breakers tripped, no obvious shorts at outlets. I have opened the drywall following the wires around hoping to find a short but I have found nothing. I decided to try something, and I bridged the working switch to a dead outlet and everything turned on. I am waiting til the daytime to follow the wires outside to the breaker box, but so far no breaks or anything.. curious if anyone has any pointers.. could the pop he heard from the track lighting have killed a breaker? its about the only thing left.
      
I have a battery operated 12v emergency light located in my basement. It has two lamps on it. I would like to remove one of them and place it upstairs in my dining room to cover that and the living room. I have some old 14/3 SO cable lying around and wondered if you guys thought if it would be acceptable to use this. Also, can I run this in the wall cavity as long as my terminations are inside the box where I mount the light? Is there any part of the code that covers this or any violation of the code?



Thanks,

Rick
      
Hi, I have a problem where if I turn off my light switch on one side of the  room, it turns off anything plugged into the electrical outlet on the  other side of the room. For some reason, they originally wired that  outlet on the same circuit as the light switch. I would like to wire the  outlet so that it does not switch off whenever you switch off the light  on the opposite wall.



How do I go about doing that? Thanks.



(p.s. There are just the basic three wires in the electrical outlet; black/white/bare copper ground).
      
Hello there,



I just installed a new fixture in my dining room. It has 5 MR16 halogen bulbs. When i turn on the light switch, the lights are gradually turning on to full brightness. The process takes a between 5 to 10 seconds.



I removed one of the bulb and noticed it took a bit less time and continued until I had only 3 bulbs and then the lights are turning on instantly.



So I think its obvious that the fixture is drawing too much power from the circuit. My question is, why? What tests can I dk to find the cause? Is it a faulty switch or faulty wiring?



Thank you!
      
With a hard wired LED closet light fixture, can it be wired like an undercabinet fixture? clamp the wire to the light and push the excess wire into the ceiling?

 

Or can i install an outlet on the ceiling and use the plug in style lights?

 

Im going to install a switch outside of the closet so there will be 1 wire going to the light.



What is the best way to do this?
      
I'm trying to fix a problem with a track light installment over the a bar I've just put in. I've done it before. never had issues. but this particular problem is driving me nuts. It just defies logic.  The electrician who actually installed the associated dimmer switches with this dining room area was called as it seems it may be a flaw with his wiring, but he's blown us off and I have to try and solve this myself.



This is how it's all set up. I've been rehabbing our home from top to bottom, and converted our old kitchen into a dining area. Within this dining area are four sets of lights, all controlled from one box containing four dimmer switches. I set up all the new wiring and installation of the lights in the ceiling, and we paid an electrician to come in, check everything out, set up the multiple switches, and connect it all to the board. It's all new copper wiring from beginning to end, as I didn't want to connect or splice in to the old aluminum wiring that was in place. All the new wiring and lights are on a dedicated 15 amp breaker. Three of the sets of lights were set up to be available from the day the electrician came around. The fourth, for the track light over the bar, was left hanging from the ceiling capped off and with the switch off, as I still had work to do installing an overhead wine rack, under which the track was going to be set.



Two days ago I finally got around to putting the track up, but after setting it in place and connecting the power up the lights wouldn't work. I took the lights out to our kitchen, where I installed another track light system some time ago, plugged one of the lights in, and it worked just fine. I then went back to the bar area and used a spare track, then a spare connector, to see if I could isolate the fault, yet neither of the items provided a solution. Now here's the weird bit - every time I tried checking the system out, I'd get 120 volts showing from the wiring and from the track when I'd test with the multimeter. But the second I'd put a light into the track, the multimeter would drop to zero on the voltage reading on either the wiring or the track. Take the light fixture back out, and the voltage would pop back up. Inserting the light was thus completing some kind of odd loop. It wasn't just one light - I double checked by grabbing working lights from the kitchen track and inserting them into the other track - the same problem would pop up. Finally, having come to the conclusion that there was nothing wrong with the track at all, I took the whole assembly over to a nearby wall outlet, used some spare electric cable to connect up to the appropriate slots - presto, the light came on! I even double checked all this by grabbing another light fixture destined for our bathroom, and tried connecting it to the wiring over the bar. Nothing. Yet as with the track light, the minute I took it over to the wall outlet and connected it, the light worked.



So everything logically points to the fact it has to be something to do with this individual circuit, right, because a) the light fixtures work when plugged into another circuit and b) the other three dimmers and lights hooked up in the same box work fine and draw power from the same wire cable/breaker combination. The only things left that I can think of is that the electrician has either wired the dimmer switch up incorrectly or that there's some kind of flaw inside the switch itself. Does this make sense?



A friend also told me to double-check to make sure that the black wire feeding power to the light was indeed the hot wire, and it is.  If I touch it with the black test lead from the multimeter and put the red one to the neutral I show 120 volts. If I keep the black test lead on the black wire and put the red test lead to the ground - I also show 120 volts.



A final point. I know I'm not overloading the circuit - not even close. With all four dimmers maxed and every light on - including the test light on the track - I'd only be drawing 8 amps on a 15 amp breaker, besides which I'm only using one set of lights while I'm working on this problem anyway. This is a dedicated circuit, so there's no additional power being drawn away by something else.



So how am I getting 120 volts from this wiring, according to my multimeter, yet it won't light up ANYTHING and keeps giving off the indication that some kind of loop or short is being created every time I actually plug a light into the track? It's got me totally stumped.



Anyone have any ideas?
      
I replaced a ceiling light with a fan/light with a remote. everthing works. their is one light switch and one dimmer switch. The dimmer switch has a red wire and a black wire connected to the black wires coming out of the dimmer switch, plus a green wire hooked to the metal portion of the dimmer. My question is: Do I have to remove the dimmer switch, if so, can I disconnect the red and black and hook them together? If I have to replace the dimmer with a regular switch, what kind of switch do I get?

Thank you
      
I have a covered (rafters, decking, shingles, etc) screen room out back. It used to have a single light, which I wanted to replace with a ceiling fan with light kit, independently switched. So I bought this fan/light dimmer: http://www.lowes.com/pd_69955-539-S2...d=10151&rpp=24



I checked the wire at the old light, and as it was 14-2, I removed it and replaced it with 14-3. It wasn't until after I spent 3 hours crawling around the attic on my stomach running the new line that it hit me....the circuit is on a 20 amp breaker. The line running to the switch, and a jumper running from it to 5 wall outlets in the living room, is all 12-2.



The new line runs straight from the switch to the fan box, with no other outlets. So while I doubt it is up to code, it seems like it should be ok. The fan/light won't pull anywhere near enough power to overheat the 14 gauge line, and if there is an actual fault, it should trip the 20 amp breaker anyway.



I would very much like to hear from the experts. Running the 14-3 was a serious pain in the butt, and replacing it with 12-3 would be just as bad. So if this is safe, I'd rather not replace it. But if I am risking a fire, it is obviously worth the hassle.